MAIN POWER SUPPLY Devices with OPTION L provide low voltage power supply input in a wide voltage range. The power supply must not be shared with other equipment and meet SELV circuit requirements according to EN/IEC62368: Suggested power source is a cheap 12VAC / 10VA transformer. Length between power supply source and device must be less than 3 m. |
|
|
voltage |
9 ... 35 VDC 9 ... 27 VAC |
|
current |
690 mA MAX |
|
output voltage |
3,3 VDC AT TERMINAL 06 |
|
|
|
|
Devices with OPTION M allow power supply from main power line. |
|
|
VOLTAGE |
85 ... 264 VAC |
|
FREQUENCY |
47 ... 63 Hz |
|
POWER |
< 5 VA |
|
CURRENT |
250 mA MAX @ 115 VAC 100 mA MAX @ 230 VAC |
|
POWER FACTOR |
0,60 @ 115VAC 0,45 @ 230VAC |
|
ISOLATION |
3 kV 1 MINUTE 4 kV 3 SECONDS |
|
|
|
|
AN AUTOMATIC 2 POLE CIRCUIT BREAKER OR EQUIVALENT PROTECTION CAPABLE OF DISCONNECTING CIRCUIT IN THE EVENT OF SHORT CIRCUIT OR OVER CURRENT SHOULD BE PROVIDED |
|