DIGITAL INPUTS

Each of the 6 digital inputs (and each of the 4 analog channels used as a digital input) has a parameter group containing resource settings and status.

Replace the letter x with the channel number 1 to 6 (and A to D for analog inputs used as digital).


Ix0

Mode

Enable / disable the digital input.

A disabled input is not detected and does not produce events.

0 = disabled / 1 = enabled - Default: enabled

Ix1

Name

Set a meaningful name representing the associated function.

4 ... 15 alphanumeric characters - Default: din1 ... din6

THE FOLLOWING PARAMETERS ARE NOT AUTOMATICALLY UPDATED IN THE CLOUD ACCOUNT (KEPT AS LOCAL) IF THE NAME STARTS WITH A POINT

INTENTIONAL PUBLICATION IS POSSIBLE WITH THE AT # SMAP COMMAND

Ix2

Status

Current status of the input.

0 means open, deactivated, off / 1 means closed, activated, on.

0 / 1

Ix3

Running counter

The accumulated time (minutes) with input closed, the counter re-starts from zero once 999999 minutes are reached

This counter (updated by device) can be reset or set at any time to an arbitrary value.

0 ... 999999 [minutes]

Ix4

Activation time

The status changes only if the input remains stable for the whole period of time set here, in the range 0 to 65535 seconds.

0 = immediate / 1 ... 65535 [seconds] - Default: 3

Ix5

Color

This optional parameter defines the color to be used by web platform to show the input channel.

red / green / yellow / blue - Default: red