ANALOG INPUTS


Each of the 4 analog inputs has a parameter group containing resource settings and status.

Replace the letter x with the channel number from 1 to 4.

Ax0

Mode

Disable or set the operating mode of the analog input.

A disabled input is not detected and does not produce events.

0 = disabilitato / 1 = abilitato - Default: disabilitato

Ax1

Name

Set a meaningful name representing the associated function.

4 ... 15 alphanumeric characters - Default: ain1 ... ain4

THE FOLLOWING PARAMETERS ARE NOT AUTOMATICALLY UPDATED IN THE CLOUD ACCOUNT (KEPT AS LOCAL) IF THE NAME STARTS WITH A POINT

INTENTIONAL PUBLICATION IS POSSIBLE WITH THE AT # SMAP COMMAND

Ax2

Average

Average value of  readings taken during the defined measurement period, scaled according to the zero and full scale settings.

Ax3

Lowest

Value of lowest measure taken during the defined measurement period, scaled according to the zero and full scale settings.

Ax4

Highest

Value of highest measure taken during the defined measurement period, scaled according to the zero and full scale settings.

Ax5

Measuring period

The period of time during which take the average, minimum and maximum values, in the range 1 to 1440 minutes (24 hours).

1 ... 1440 [minutes] - Default: 1

Ax6

Unit

Measuring unit associated with this channel, free text up to 5 characters.

Ax7

Full scale

Value returned for full scale readings.

Set 500 for a load cell that returns 10V once loaded with 500 kg.

Set -10 for a sensor returning 20mA at a depth of 10 meters.

Adjustable in the range from ± 1 to ± 1000000.

±1 ... ±1000000 - Default: 10

Ax8

Zero

Value read from input for zero indication.

Set 4 for a 4...20mA sensor.

Set 2 for a 2 ...10 V sensor.

0 ... 20.9 - Default: 0

Ax9

Instant

Value read in real time at the time of the request. This is the average value of the measurements made in the last second of the measurement (about 4 samples).