PULSE COUNTER INPUTS Each of the 6 pulse counter inputs has a group of parameters containing resource settings and status. Replace the letter x with the channel number from 1 to 6. |
|
|
Px0 |
Mode Enable / disable the pulse counter input. A disabled input is not detected and does not produce events. 0 = disabled / 1 = enabled - Default: disabled |
|
Px1 |
Name Set a meaningful name representing the associated function. 4 ... 15 alphanumeric characters - Default: pin1 ... pin6 |
|
THE FOLLOWING PARAMETERS ARE NOT AUTOMATICALLY UPDATED IN THE CLOUD ACCOUNT (KEPT AS LOCAL) IF THE NAME STARTS WITH A POINT INTENTIONAL PUBLICATION IS POSSIBLE WITH THE AT # SMAP COMMAND |
|
|
Px2 |
Total counts Total number of accumulated counts, the counter re-starts from zero once 999999 counts are reached. This counter (updated by device) can be reset or set at any time to an arbitrary value. 0 ... 999999 |
|
Px3 |
Period counts Counts accumulated during the defined measurement period, the counter re-starts from zero once 999999 counts are reached. This counter (updated by device) can be reset or set at any time to an arbitrary value. 0 ... 999999 |
|
Px4 |
Measuring period The period of time during which a partial count is detected, in the range 1 to 1440 minutes (24 hours). While the total count is associated with energy, the partial count can be associated with power or flow. 1 ... 1440 [minutes] - Default: 1 |
|
Px5 |
Unit Measuring unit associated with this channel, free text up to 5 characters. |
|
Px6 |
Pulses per count Set how many pulses detected at the input are necessary to increase the count of 1. 1 ... 100 - Default: 1 |