OUTPUTS


Up to 4 SPST relay contacts are available for process or appliance control at terminal 17-20. Status is reported on LED indicators [D].

Common return at terminal 16.



RATED CURRENT

3 A cosφ=1

1 A cosφ=0,6

RATED VOLTAGE

250 VAC

BREAKING voltage

277 VAC

MAX BREAKING CAPACITY

750 VA

INSULATION TO IEC60664

Voltage rating 277 V

Category as basic insulation III

Category as reinforced insulation II 

surge voltage coil-contacts 5000 VRMS

DIELECTRIC STRENGTH

coil-contacts 3000 VRMS

open contacts 750 VRMS



TO PREVENT RELAY CONTACTS FROM DAMAGING, AN EXTERNAL PROTECTION SHOULD BE PROVIDED (FUSE OR SIMILAR), ACCORDING TO THE RELAY BREAKING CAPACITY.