ANALOG INPUTS Each of the 4 analog inputs has a parameter group containing resource settings and status. Replace the letter x with the channel number from 1 to 4. |
|
Ax0 |
Mode Disable or set the operating mode of the analog input. A disabled input is not detected and does not produce events. 0 = disabilitato / 1 = abilitato - Default: disabilitato |
Ax1 |
Name Set a meaningful name representing the associated function. 4 ... 15 alphanumeric characters - Default: ain1 ... ain4 |
THE FOLLOWING PARAMETERS ARE NOT AUTOMATICALLY UPDATED IN THE CLOUD ACCOUNT (KEPT AS LOCAL) IF THE NAME STARTS WITH A POINT INTENTIONAL PUBLICATION IS POSSIBLE WITH THE AT # SMAP COMMAND |
|
Ax2 |
Average Average value of readings taken during the defined measurement period, scaled according to the zero and full scale settings. |
Ax3 |
Lowest Value of lowest measure taken during the defined measurement period, scaled according to the zero and full scale settings. |
Ax4 |
Highest Value of highest measure taken during the defined measurement period, scaled according to the zero and full scale settings. |
Ax5 |
Measuring period The period of time during which take the average, minimum and maximum values, in the range 1 to 1440 minutes (24 hours). 1 ... 1440 [minutes] - Default: 1 |
Ax6 |
Unit Measuring unit associated with this channel, free text up to 5 characters. |
Ax7 |
Full scale Value returned for full scale readings. Set 500 for a load cell that returns 10V once loaded with 500 kg. Set -10 for a sensor returning 20mA at a depth of 10 meters. Adjustable in the range from ± 1 to ± 1000000. ±1 ... ±1000000 - Default: 10 |
Ax8 |
Zero Value read from input for zero indication. Set 4 for a 4...20mA sensor. Set 2 for a 2 ...10 V sensor. 0 ... 20.9 - Default: 0 |
Ax9 |
Instant Value read in real time at the time of the request. This is the average value of the measurements made in the last second of the measurement (about 4 samples). |
Wake-up threshold from power saving If the device operates in SLEEP mode, it will wake up if the analog input measurement exceeds this threshold (both rising and falling). ±1 ... ±1000000 - Default 0 (disabled) |