WIEGAND This group contains information and settings associated with the interface for a Wiegand device. |
|
K00 |
Mode OFF : disable Wiegand interface at digital inputs I1 and I2. 1: AUTO, recognize any valid Wiegand string returned code includes also parity bits (raw format) 2: 26bit, recognize only 26 bit codes retuned code without parity bits from firmware version 02.29 3: 34bit, recognize only a 34 bit codes retuned code without parity bits from firmware version 02.29 Default: OFF |
K01 |
Last code The last code received from the Wiegand device. |
K02 |
2nd last code The second last code received from the Wiegand device. |
K03 |
3rd last code The third last code received from the Wiegand device. |
K04 |
4th last code The fourth last code received from the Wiegand device. |
K05 |
5th last code The fifth last code received from the Wiegand device. |
K06 |
6th last code The sixth last code received from the Wiegand device. |
K07 |
Last group The group to which the last code received from the Wiegand device belongs. If not stored as user, the parameter will be empty. |