Mobi.Control provides two special digital inputs at screw terminals 17 and 18. These inputs can be used as a standard digital input in addition to the 8 channels already available (without LED indication). Independent activation (debounce) time can be set in range of 1 to 300 seconds. Inputs can operate also as a pulse or time counter. SPST contacts, magnetic reed, hall sensor or electronic switches can be used. Pulse width configurable for mechanical (200ms) or electronic (20ms) sensor. |
|
Input voltage range |
3...9 Vdc |
Input current |
5mA @ 5V |
Debounce time |
1...300 seconds |
Pulse width |
> 200 ms / 20 ms configurable |
Frequency |
< 2,5 Hz |
Input supply voltage |
3,3 Vdc at terminal 04 |
External power supply for inputs must meet SELV circuits requirements according to EN60950/IEC950: maximum allowed voltage is 60Vdc |