Mobi.Control has 8 digital inputs accessible at terminals 05 to 12. Orange LED on the front of the unit report their status. A 3,3Vdc power supply for these inputs is available at terminal 04. If electronic switches are used, please connect positive terminal of the switches to terminal 04. |
|
Input voltage range |
3...9 Vdc |
Input current |
5mA @ 5V |
Debounce time |
1...300 seconds |
Input supply voltage |
3,3 Vdc at terminal 04 |
If switches are supplied by an external power supply, negative terminal must be connected to terminal 01. A zener diode can provide an easy solution to keep input voltage in the 9Vdc range. The following figure shows some possible wiring diagram. |
|
- Inputs 1 and 2 uses the internal 3,3 Vdc power supply. - Inputs 3 and 4 uses an external 5 Vdc power supply (no zener diode is required). - Inputs 5 and 6 uses an external 12 Vdc and a 6,8V zener diode reduces the input voltage. - Inputs 7 and 8 uses an external 24 Vdc and a 20V zener diode reduces the input voltage. |
External power supply for inputs must meet SELV circuits requirements according to EN60950/IEC950: maximum allowed voltage is 60Vdc |